Department Of Logistics And Infrastructure
Darwin Region - Bakewell Primary School - Mechanical Demolition and Equipment Installation Upgrade the Withdrawal/Teachers Prep rooms of Blocks A & B and the Community Room at Bakewell Primary School from standalone DX systems to chilled water based air conditioning systems, consistent with the site chilled water strategy.
electronic meter, mechanical meter or inclined manometer with full scale not more than 400 measured value, accuracy better than 2. 5 full scale. water pressure and differential pressuresinstrument specifications: accuracy: better than 1 of full scale. scale: not more than 400 measured value. temperatureair temperature instruments specifications: accuracy: 0. 2k or better at measured value. chilled water and condenser water temperature instrument specification: accuracy: 0. 2k or better at measured value. instrument specifications for other temperature applications: accuracy: 0. 5k or better at measured value. scale divisions mercuryinglass: 1. 0k or better. humidityinstruments specifications: sling psychrometer, aspirated psychrometer or electronic humidity meter. accuracy: 3 from 10 to 90 relative humidity where measured value tolerance is5 relative humidity. half measured value tolerance from 10 to 90 relative humidity where measured value tolerance is